Most data center cooling discussions focus on the white space. But the servers depend on the systems behind them: the central plant that supplies chilled water, the generators that keep power on during an outage, and the fire and smoke controls that protect equipment and people. If any one of them fails, uptime is at risk.
Belimo’s facility solutions and central plant controls cover all three. This is the last post in our data center series, following our posts on air cooling, liquid cooling, and the standard in data center cooling. For a broader look at the product line, see our overview of Belimo valves, actuators, and energy monitoring for data center HVAC.
Table of Contents
Data Center Facility Solutions and Central Plant Controls
Data center reliability depends on more than the IT equipment. According to Belimo’s Data Center Cooling Solutions brochure, Belimo controls are used across central plants, chillers, heat rejection systems, generators, and fire and smoke safety to help facility managers improve performance, minimize downtime, and meet sustainability targets. Real-time data and integration with your building automation system (BAS) make that possible.
Chiller and Heat Rejection
The central plant supplies chilled water to the entire data center. At these cooling loads, that takes high flow rates and large valves.
Belimo butterfly valves with high-performance actuators are a strong fit for this job because of their high close-off pressure, low leakage rates, and NEMA 4 enclosures. They are available in 2-way and 3-way configurations from 2 to 24 inches and are used for central plant, header, and isolation valve applications, including chiller and cooling tower isolation. The electronic actuators are maintenance-free. Close-off pressure varies by valve series, size, and actuator, so check the rating against your design differential pressure using Belimo’s butterfly valve technical documentation.
-
F650HD+ARX24-MFT
-
F6100HD+DRX24-MFT-T
-
F6125HD+DKRX24-3-T
-
F6150HDU+DRX24-MFT-T
-
F665HD+ARX24-3
-
F6150HD+PKRXUP-MFT-T
-
F6100VIC+DRCX24-3-T
-
F680HDU+ARX24-3
-
F680HD+GRCX24-3-T N4
-
F680-150SHP+PRBUP-3-T
-
F665HD+AFRXUP-S
-
F6200-150SHP+SY4-110
-
F6150HD+PRXUP-3-T
-
F6150HD+PRBUP-3-T
-
F6125HD+PRBUP-3-T
-
F6125HD+HND02
-
F6100HD+DRCX24-3-T
-
F6100HD+DKRX24-MFT-T
-
F6150HDU+DRB24-MFT-T
-
F7200L+PRXUP-MFT-T-200
-
F7200L+PRBUP-MFT-T-200
-
F7150HDU+2*GMX24-MFT-X1
-
F7100HDU+2*GMX24-MFT-X1
-
F680HDU+ARX24-MFT
For visibility into the plant, Belimo flow meters, temperature sensors, and thermal energy meters provide real-time flow, temperature, and energy data. For the equipment the plant supports, see our posts on air cooling and liquid cooling.
Key Specifications
- Leakage rate: Features an intelligent self-adjusting end stop algorithm that ensures 0% leakage (bubble-tight shut-off) at up to 200 psi close-off pressure, preventing energy loss during chiller isolation.
- Energy efficiency: Actuators utilize patented brushless DC motor technology, which reduces power consumption by up to 80% compared to traditional models, lowering both transformer and wiring costs.
- Enclosure ratings: Designed with NEMA 4X (IP66/IP67) housings to protect against UV radiation, rain, snow, dirt, and humidity, making them ideal for outdoor cooling tower environments.
- Integration and commissioning: Built with native BACnet, Modbus, and MP-Bus protocols, plus integrated Near Field Communication (NFC) that allows for fast setup, troubleshooting, and diagnostics via a smartphone even when the actuator is unpowered.
- Valve capacity: Available in sizes ranging from 2” to 24” with ASME/ANSI Class 150 or 300 ratings, offering high Cv values designed specifically for large, high-flow mechanical applications.
Generators
Generators keep servers running when utility power fails, and every generator set depends on a steady supply of air. One engineering reference puts the radiator cooling airflow at typically 15 to 20 times the airflow needed for combustion. NFPA 110 includes requirements for that air, as outlined in this overview of generator system design.
Belimo fail-safe actuators control the precise amount of combustion air a generator needs. If there is an issue, fail-safe operation lets airflow be shut off immediately. NEMA 4 options are available when the actuators are installed outside the generator. Damper arrangements on generator air paths are subject to NFPA 110 and local requirements, so confirm the details with the engineer of record.
Belimo damper actuators range from 9 to 1,400 in-lbs and also serve CRAH, fan wall, and outside air applications, which we cover in our air cooling post.
Key Specifications
- Motor technology: Utilizes highly efficient brushless DC motors, which significantly reduce power consumption, minimize heat generation, and extend the overall lifespan of the actuator.
- Customization: Features Belimo’s Multi-Function Technology (MFT), allowing technicians to field-configure control signals (analog, PWM, floating point), feedback, and running times.
- Fail-safe options: Available in both mechanical spring-return and electronic (SuperCap) fail-safe models to ensure dampers return to a designated safe position during a power loss.
- Torque range: Offers a wide variety of torque options (typically from 18 in-lbs to 360 in-lbs) to accommodate both standard and heavy-duty damper applications.
Fire and Smoke
Belimo fire and smoke damper actuators are safety devices that protect data centers from fire and smoke hazards. They integrate with fire and smoke detection systems and control dampers to limit the spread of fire and smoke in an emergency.
Key Specifications
- Listings: The actuators are tested with the damper as an assembly to UL 555 and UL 555S. Belimo’s specification also calls for UL 2043 listing for low smoke generation in plenum spaces.
- Cycle life: Exceeds UL’s requirement of 20,000 cycles at damper static load.
- Heat resistance: An internal, heat-resistant spring closes the damper without loss of torque at elevated temperatures.
- Testing: The FSKN BACnet remote inspection module allows testing of actuated life safety dampers without visually inspecting each one, and Belimo states it meets NFPA 80 and NFPA 105 testing requirements.
See the FSAF24A-S datasheet for more information.
Belimo Facility and Central Plant Components from Boston Aircontrols
New construction or retrofit, Boston Aircontrols carries a complete line of Belimo actuators, sensors, and valves, with expert quoting and support. As New England’s #1 Belimo distributor, we have the inventory, expertise, and fast turnaround to help you find the right solutions for your data center project.