Damper actuators sit at the center of HVAC airflow control. They position the dampers in air handlers, VAV terminal units, fan coil units, and economizers, and their reliability affects comfort, energy use, and life safety. Belimo damper actuators cover torque ranges from 9 to 1,400 in-lb and are built for dampers as small as 4-inch round, with direct mounting on standard damper shafts or jackshafts.
This guide covers the four main Belimo damper actuator categories, what separates them, and the questions to answer when selecting one for a project.
Table of Contents
Belimo Damper Actuator Applications
Dampers regulate airflow throughout a building, and the actuators that drive them determine how precisely and reliably an HVAC system performs. Belimo damper actuators are designed for a wide range of HVAC applications, including:
- Control dampers
- Air handlers
- Economizer units
- VAV terminal units
- Fan coil units
- Fan shutters
- Unit ventilators
Across these applications, Belimo actuators share a common technology foundation: brushless DC motors, direct communication with building automation systems, and a 5-year warranty. The Core Technology Across the Line section covers these shared features in detail.
Core Technology Across the Line
| Brushless DC Motor with ASIC Control | Brushless DC motor managed by an Application Specific Integrated Circuit (ASIC). Delivers consistent torque over the entire operating range, with no performance loss from temperature, supply voltage, or speed. Also provides stall protection and lower power consumption. |
| Building Automation Communication | Communicates directly with the Building Automation System (BAS) using BACnet, Modbus, or MP-Bus. Select models add Near Field Communication (NFC) for programming, commissioning, and troubleshooting. |
| Harsh-Environment Housings | Select models offer weather-tight, corrosion-resistant NEMA 4 and 4X housings with UV protection for outdoor use. A heater option supports high-humidity or low-temperature (-40°F) applications. |
| Warranty | 5 years |
Non Fail-Safe Damper Actuators
Belimo’s non fail-safe damper actuators suit a broad range of HVAC damper applications. They offer torque ratings from 9 in-lb up to 1400 in-lb and mount directly onto standard damper shafts or jackshafts. That flexibility makes them a strong fit for operating the dampers in built-up and packaged air handlers, VAV terminal units, fan coil units, and unit ventilators, including those installed in hospitals, schools and universities, and data centers.
Specifications
| Torque Range | 9 in-lb to 1,400 in-lb, available in rotary and linear versions |
| Mounting | Direct mount on standard damper shafts or jackshafts, with a universal clamp that fits a wide range of shaft sizes |
| Speed | Quick-running models complete a 90° rotation in 2.5 seconds at 35 in-lb, or in 7 seconds at 140 in-lb |
| Control Types | On/off, floating point, 2-10 V, phasecut, Multi-Function Technology (MFT), BACnet/IP, Modbus TCP, BACnet MS/TP, and Modbus RTU |
| Warranty | 5 years |
Features
| Universal Clamp | Accommodates a wide variety of damper shafts, simplifying installation |
| Patented Brushless DC Motor Technology | Built for dependable operation over a long service life, well beyond the 5-year warranty period |
| Consistent Torque | Output holds steady across the full operating range, with no performance loss from changes in temperature, supply voltage, or speed |
| Flexible Signal Options | Choose from multiple control types, or use Multi-Function Technology to go from individual parameter settings all the way to complete system integration, which can help reduce costs |
| Adjustable End Stops | Lets installers set the rotational range precisely, adding flexibility during installation |
| Switchable Direction of Rotation | Adapts to different damper configurations |
| Manual Override | Allows the damper to be positioned by hand when needed |
Understanding the Non Fail-Safe Model Number

Example Belimo Non-Fail Safe Damper Actuator Model Number
| LM | Q | B | 24 | -1 |
Belimo Non-Fail Safe Damper Actuator Model Number Key
| Torque Rating | Speed | Version | Power Required | Control | Options | |
|---|---|---|---|---|---|---|
| Non-Fail Safe Rotary | Q = Quick Running | B = Basic | 14 = AC/DC 24 V, 50/60 Hz | -1 = On/Off | -T = Terminal Block | .1 = Bulk Pack |
| PM = 1400 in-lb | C = Fast Running | X = Customized | 120 = AC 100…240 V 50/60 Hz | -3 = On/Off, Floating Point | Blank = Cable Version | N4 = NEMA 4/4X |
| GM = 360 in-lb | No Designation = Normal Speed (LMB24-3) | UP = AC 24…240 V* | -3-P5 = On/Off, Floating Point w/5k Ω Feedback | -S = Switch | X…N4 Types | |
| AM = 180 in-lb | -3-P10 = On/Off, Floating Point w/10k Ω Feedback | Y = Heater Option | ||||
| NM = 90 in-lb | -SR = 2…10 V | |||||
| LM = 45 in-lb | -PC = Phasecut (0.5…20 V) | |||||
| CM = 18 in-lb | -MFT = Multi-Function Technology | |||||
| UM = 9 in-lb | -MFT95 = 0…135 Ω | |||||
| Non Fail-Safe Linear | IP = BACnet/IP, Modbus TCP | |||||
| AH = 100 lbf | MOD = BACnet MS/TP, Modbus RTU | |||||
| LH = 34 lbf |
Note: Q versions have a slightly lower torque rating. *DC 24…125 V
Fail-Safe Damper Actuators
Belimo’s fail-safe damper actuators cover a broad torque range, from 22 in-lb up to 1,400 in-lb. They couple directly to the damper and offer rotary or linear travel, which lets them serve many different HVAC applications. Each actuator runs on a brushless DC motor managed by an Application Specific Integrated Circuit (ASIC). This design protects the motor against stalling, draws less power, and operates more efficiently, so installers can also specify a smaller transformer. For added versatility, a range of accessories gives you more choices for mounting and commissioning.
There are two series:
- Mechanical fail-safe (EF, AF, NF, LF, TF series): 22 to 270 in-lb, with optional built-in auxiliary switch, NEMA 4/4X models, and heater option.
- Electronic fail-safe (NK, GK, PK, AHK series): 54 to 1,400 in-lb, plus a 100 lbf linear model. These use patented super capacitor technology.
Why it matters
- Electronic fail-safe models offer fail position options (0–100%) that delay unnecessary actuator movement during short brownouts, which avoids changes in the HVAC system and BAS.
- Electronic overload protection increases actuator longevity and reduces maintenance cost.
- ASIC-based motor control reduces energy consumption and allows smaller transformer sizing.
- Multi-Function Technology models offer proportional control functions and DC voltage feedback signals, set at the factory or adjusted in the field.
Specifications
| Torque Range | 22 in-lb to 1,400 in-lb |
| Coupling and Travel | Direct-coupled, with rotary, linear, and quick-running versions |
| Motor Technology | Patented brushless DC motor controlled by an Application Specific Integrated Circuit (ASIC) |
| Control Types | Analog, BACnet MS/TP, and Modbus RTU, plus Multi-Function Technology (MFT) models |
| Fail Position | Adjustable from 0 to 100% on electronic fail-safe models |
| Signals | Proportional control functions and DC voltage feedback, factory-programmed or adjustable in the field |
| Accessories | A variety of options for mounting and commissioning |
Features
| Options for Demanding Applications | Rotary, linear, and quick-running models are available for challenging installations. |
| Energy Savings and Longevity | The patented motor and ASIC combination lowers energy consumption and extends actuator life. |
| Stall Protection | The ASIC-controlled motor guards against stalling. |
| Smaller Transformer Sizing | Lower power draw allows for smaller transformers. |
| Multi-Function Technology | MFT models offer many proportional control functions and DC voltage feedback signals, set at the factory or tuned in the field. |
| Brownout ride-through | Electronic fail-safe models let you set a fail position that delays needless actuator movement during short brownouts, which prevents disruptions to the HVAC system and building automation system (BAS). |
| Overload protection | Electronic protection against overload extends actuator life and reduces maintenance costs. |
| Industry-standard compatibility | Control types work with common standards such as analog, BACnet MS/TP, and Modbus RTU. |
| Accessory flexibility | Accessories add mounting and commissioning options across applications. |
Understanding the Fail-Safe Model Number

Example Belimo Mechanical Fail Safe Damper Actuator Model Number
| EF | X | 24 | -MFT | -S | N4 |
Belimo Mechanical Fail-Safe Damper Actuator Model Number Key
| Torque Rating | Speed✝ | Version | Power Required | Control | Options | |
|---|---|---|---|---|---|---|
| EF = 270 in-lb | C = Fast Running | B = Basic | 24 = AC/DC 24 V | Blank = On/Off | -S = Built-in Auxiliary Switch | US |
| AF = 180 in-lb | L = Low Noise | X = Customized | 120 = AC 120 V* | -3 = Floating Point | EF…Series | |
| NF = 90 in-lb | Blank = Normal Speed | Blank = None | 230 = AC 230 V | -SR = 2…10 V | N4♦︎ = NEMA 4/4X | |
| LF = 35 in-lb | UP = AC 24…240 V** | -PC = Phasecut (0.5…20 V) | X…N4 Types | |||
| TF = 22 in-lb | -ECON-RO3 = 3k W NTC Type 10 Thermistor | H = Heater Option | ||||
| -MFT = Multi-Function Technology | ||||||
| -MFT95 = 0…135 Ω | ||||||
| -MFT-20 = 6…9 V, 20 V Power Supply | ||||||
| -IP = BACnet/IP, Modbus TCP | ||||||
| -MOD = BACnet MS/TP, Modbus RTU |
♦︎ NEMA 4 option on select models.
✝ Only available on certain LF and TF models.
*EF and TF series have AC 100…240 V nominal power supply.
**DC 24…125 V.
Example Belimo Electronic Fail Safe Damper Actuator Model Number
| NK | Q | X | 24 | -MFT |
Belimo Electronic Fail-Safe Damper Actuator Model Number Key
| Torque Rating | Speed | Version | Power Required | Control | Options |
|---|---|---|---|---|---|
| PK = 1400 in-lb | Q = Quick Running | B = Basic | 24 = AC/DC 24 V* | -1 = On/Off | -T = Terminal Block |
| GK = 360 in-lb | Blank = Normal Speed | X = Customized | UP = AC 24…240 V** | -3 = On/Off, Floating Point | N4♦︎ = NEMA 4/4X |
| NK = 54 in-lb | -SR = 2…10 V | X…N4 Types | |||
| AHK = 100 lbf | -MFT = Multi-Function Technology | Y = Heater Option | |||
| -IP = BACnet/IP, Modbus TCP | |||||
| -MOD = BACnet MS/TP, Modbus RTU |
♦︎ NEMA 4 option on select models.
*GK..24-3 is AC 24 V only.
**DC 24…125 V
Fire and Smoke Damper Actuators
The fire and smoke line includes four torque ratings (18, 30, 70, and 180 in-lb), 24 V, 120 V, and 230 V power options, built-in auxiliary switches, and a modulating fail-safe model at 180 in-lb. Linkage kits are available for indirect mounting and pneumatic retrofit projects. These actuators can be controlled from a central location and integrated into building safety systems, which supports smoke control that lets occupants exit and firefighters enter.
Specifications
| Applications | Fire dampers, smoke dampers, and combination fire and smoke dampers in ventilation and air-conditioning systems |
| Torque range | 18 in-lb to 180 in-lb at 350°F |
| Code compliance | Meets all U.S. codes for commercial buildings |
| UL certification | Passes UL 555 and UL 555S at 350°F |
| Cycle testing | Tested for 30,000 open-closed cycles with approved dampers, exceeding UL’s 20,000-cycle requirement at damper static load |
| Quality control | ISO 9001 certified |
| Warranty | 5 years |
Features
| Efficient microcontroller-driven motors | Belimo’s microcontrollers let the motors produce high torque at low current draw, and they run cooler, which extends service life |
| Reliable operation and support | ISO 9001 certified quality control and a 5-year warranty back the actuators with dependable performance and strong customer support |
| Central control and safety system integration | Actuators can be operated from a central location and tied into safety systems, helping keep the environment relatively smoke-free so occupants can exit efficiently and firefighters can enter |
| Life safety compliance | Compliant with Life Safety Codes and Standards |
| Maximum safety | Designed to meet code requirements in all situations, with cycle testing that surpasses the UL minimum |
Understanding the Fire and Smoke Model Number

Example Belimo Fire and Smoke Damper Actuator Model Number
| FS | N | F | 24 | -S |
Belimo Fire and Smoke Damper Actuator Model Number Key
| Fire and Smoke | Torque Rating | Actuator Type | Power Supply | Generation | Control | Options |
|---|---|---|---|---|---|---|
| FS = Fire and Smoke | A = 180 in-lb | F = Fail-Safe | 24 = AC/DC 24 V* | Blank = Original | Blank = On/Off | -S = Built-in Auxiliary Switches |
| N = 70 in-lb | FB = Fail-Safe, Modulating (180 in-lb only) | 120 = AC 120 V* | A = New Generation On/Off | -SR = 2…10 V* | ||
| L = 30 in-lb | 230 = AC 230 V | |||||
| AHK = 100 lbf | ||||||
| T = 18 in-lb |
* Available with FSAFB24-SR & FSAFB24-SR-S only.
Quick Comparison
| Category | Torque range | Typical use | Notable features |
|---|---|---|---|
| Non fail-safe | 9–1,400 in-lb | Air handlers, VAV, fan coil, unit ventilators | MFT, adjustable end stops, quick-running options |
| Airflow measurement and control | 18–90 in-lb (rotary and in-duct), 34 lbf (linear) | CAV and VAV systems | Integrated pressure sensor, pressure independent, NFC |
| Fail-safe | 22–1,400 in-lb | Applications requiring a defined position on power loss | Super capacitor, fail position options, overload protection |
| Fire and smoke | 18–180 in-lb at 350°F | Fire, smoke, and combination dampers | UL 555/555S, 30,000-cycle testing, auxiliary switches |
How to Choose the Right Damper Actuator
Whether you’re specifying actuators for a new build or replacing one that has failed or gone out of production, the selection process is the same. If you’re retrofitting, start by locating the part number and model on the existing actuator’s nameplate or in the old equipment manuals. That tells you what the unit does today, and most of the questions below can be answered from it. For more on that scenario, see our guide to selecting an actuator for a retrofit.
Work through these questions before specifying a model:
- What torque does the damper require?
Size the actuator to the damper’s torque requirement. Quick-running versions have a slightly lower torque rating, so factor that in if speed matters. - Is fail-safe actuation required?
If the damper needs a defined position on power loss, specify a fail-safe actuator. If the application is code-driven fire or smoke protection, specify a listed fire and smoke actuator. On a retrofit, check whether the original unit was spring return or fail-safe, and match it. - Is airflow measurement needed at the damper?
Pressure independent airflow actuators can remove the manual balancing step. - What control signal does the BAS use?
Match the actuator to on/off, floating point, 2-10 V, MFT, BACnet, or Modbus. A new actuator has to speak the same language as your control system, so confirm compatibility before you order. - What supply voltage is available?
Options include 24 V AC/DC, 120 V, 230 V, and universal power supply on select models. In a retrofit, the voltage already at the damper often decides this for you. - Can you direct couple to the damper shaft?
Belimo actuators mount directly on standard damper shafts or jackshafts. Confirm the shaft size and type, and note that accessories can add mounting and commissioning options when the fit isn’t straightforward. - What is the installation environment?
Outdoor, high-humidity, and low-temperature locations may call for NEMA 4/4X housings or the heater option.
Frequently Asked Questions
What torque range do Belimo damper actuators cover?
The line covers 9 to 1,400 in-lb across rotary and linear models, suited to damper sizes as small as 4-inch round.
What is the difference between fail-safe and non fail-safe actuators?
Fail-safe actuators move the damper to a set position when power is lost. Non fail-safe actuators stay in their last position.
Which Belimo actuators communicate with a building automation system?
Select models in each category communicate over BACnet, Modbus, or MP-Bus, and select models add NFC for commissioning.
What warranty applies to Belimo damper actuators?
Belimo provides a 5-year warranty.
Are there actuators rated for outdoor or extreme conditions?
Yes. Select models have NEMA 4 and 4X housings with UV protection, and a heater option supports high-humidity and -40°F applications.
Need Help Choosing the Correct Actuator?
Belimo model numbers follow a consistent code covering torque rating, speed, version, power requirement, control type, and options. Matching each position of the code to your project requirements narrows the selection quickly. Contact us for assistance with specifying the correct model for your project.

Unlock Exclusive Pricing
Create your free account to unlock the best Belimo pricing on the internet with exclusive shipping rates on every order.