Belimo Damper Actuators Key Features and Specifications

Share

Belimo Damper Actuators Key Features and Specifications

Damper actuators sit at the center of HVAC airflow control. They position the dampers in air handlers, VAV terminal units, fan coil units, and economizers, and their reliability affects comfort, energy use, and life safety. Belimo damper actuators cover torque ranges from 9 to 1,400 in-lb and are built for dampers as small as 4-inch round, with direct mounting on standard damper shafts or jackshafts.

This guide covers the four main Belimo damper actuator categories, what separates them, and the questions to answer when selecting one for a project.

Belimo Damper Actuator Applications

Dampers regulate airflow throughout a building, and the actuators that drive them determine how precisely and reliably an HVAC system performs. Belimo damper actuators are designed for a wide range of HVAC applications, including:

  • Control dampers
  • Air handlers
  • Economizer units
  • VAV terminal units
  • Fan coil units
  • Fan shutters
  • Unit ventilators

Across these applications, Belimo actuators share a common technology foundation: brushless DC motors, direct communication with building automation systems, and a 5-year warranty. The Core Technology Across the Line section covers these shared features in detail.

Core Technology Across the Line

Brushless DC Motor with ASIC ControlBrushless DC motor managed by an Application Specific Integrated Circuit (ASIC). Delivers consistent torque over the entire operating range, with no performance loss from temperature, supply voltage, or speed. Also provides stall protection and lower power consumption.
Building Automation CommunicationCommunicates directly with the Building Automation System (BAS) using BACnet, Modbus, or MP-Bus. Select models add Near Field Communication (NFC) for programming, commissioning, and troubleshooting.
Harsh-Environment HousingsSelect models offer weather-tight, corrosion-resistant NEMA 4 and 4X housings with UV protection for outdoor use. A heater option supports high-humidity or low-temperature (-40°F) applications.
Warranty5 years

Non Fail-Safe Damper Actuators

Belimo’s non fail-safe damper actuators suit a broad range of HVAC damper applications. They offer torque ratings from 9 in-lb up to 1400 in-lb and mount directly onto standard damper shafts or jackshafts. That flexibility makes them a strong fit for operating the dampers in built-up and packaged air handlers, VAV terminal units, fan coil units, and unit ventilators, including those installed in hospitals, schools and universities, and data centers.

Specifications

Torque Range9 in-lb to 1,400 in-lb, available in rotary and linear versions
MountingDirect mount on standard damper shafts or jackshafts, with a universal clamp that fits a wide range of shaft sizes
SpeedQuick-running models complete a 90° rotation in 2.5 seconds at 35 in-lb, or in 7 seconds at 140 in-lb
Control TypesOn/off, floating point, 2-10 V, phasecut, Multi-Function Technology (MFT), BACnet/IP, Modbus TCP, BACnet MS/TP, and Modbus RTU
Warranty5 years

Features

Universal ClampAccommodates a wide variety of damper shafts, simplifying installation
Patented Brushless DC Motor TechnologyBuilt for dependable operation over a long service life, well beyond the 5-year warranty period
Consistent TorqueOutput holds steady across the full operating range, with no performance loss from changes in temperature, supply voltage, or speed
Flexible Signal OptionsChoose from multiple control types, or use Multi-Function Technology to go from individual parameter settings all the way to complete system integration, which can help reduce costs
Adjustable End StopsLets installers set the rotational range precisely, adding flexibility during installation
Switchable Direction of RotationAdapts to different damper configurations
Manual OverrideAllows the damper to be positioned by hand when needed

Understanding the Non Fail-Safe Model Number

Damper actuator diagram

Example Belimo Non-Fail Safe Damper Actuator Model Number

LMQB24-1

Belimo Non-Fail Safe Damper Actuator Model Number Key

Torque RatingSpeedVersionPower RequiredControlOptions
Non-Fail Safe RotaryQ = Quick RunningB = Basic14 = AC/DC 24 V, 50/60 Hz-1 = On/Off-T = Terminal Block.1 = Bulk Pack
PM = 1400 in-lbC = Fast RunningX = Customized120 = AC 100…240 V 50/60 Hz-3 = On/Off, Floating PointBlank = Cable VersionN4 = NEMA 4/4X
GM = 360 in-lbNo Designation =
Normal Speed
(LMB24-3)
UP = AC 24…240 V*-3-P5 = On/Off, Floating Point w/5k
Ω Feedback
-S = SwitchX…N4 Types
AM = 180 in-lb-3-P10 = On/Off, Floating Point
w/10k Ω Feedback
Y = Heater Option
NM = 90 in-lb-SR = 2…10 V
LM = 45 in-lb-PC = Phasecut (0.5…20 V)
CM = 18 in-lb-MFT = Multi-Function Technology
UM = 9 in-lb -MFT95 = 0…135 Ω
Non Fail-Safe LinearIP = BACnet/IP, Modbus TCP
AH = 100 lbfMOD = BACnet MS/TP, Modbus RTU
LH = 34 lbf

Note: Q versions have a slightly lower torque rating. *DC 24…125 V

Fail-Safe Damper Actuators

Belimo’s fail-safe damper actuators cover a broad torque range, from 22 in-lb up to 1,400 in-lb. They couple directly to the damper and offer rotary or linear travel, which lets them serve many different HVAC applications. Each actuator runs on a brushless DC motor managed by an Application Specific Integrated Circuit (ASIC). This design protects the motor against stalling, draws less power, and operates more efficiently, so installers can also specify a smaller transformer. For added versatility, a range of accessories gives you more choices for mounting and commissioning.

There are two series:

  • Mechanical fail-safe (EF, AF, NF, LF, TF series): 22 to 270 in-lb, with optional built-in auxiliary switch, NEMA 4/4X models, and heater option.
  • Electronic fail-safe (NK, GK, PK, AHK series): 54 to 1,400 in-lb, plus a 100 lbf linear model. These use patented super capacitor technology.

Why it matters

  • Electronic fail-safe models offer fail position options (0–100%) that delay unnecessary actuator movement during short brownouts, which avoids changes in the HVAC system and BAS.
  • Electronic overload protection increases actuator longevity and reduces maintenance cost.
  • ASIC-based motor control reduces energy consumption and allows smaller transformer sizing.
  • Multi-Function Technology models offer proportional control functions and DC voltage feedback signals, set at the factory or adjusted in the field.

Specifications

Torque Range22 in-lb to 1,400 in-lb
Coupling and TravelDirect-coupled, with rotary, linear, and quick-running versions
Motor TechnologyPatented brushless DC motor controlled by an Application Specific Integrated Circuit (ASIC)
Control TypesAnalog, BACnet MS/TP, and Modbus RTU, plus Multi-Function Technology (MFT) models
Fail PositionAdjustable from 0 to 100% on electronic fail-safe models
SignalsProportional control functions and DC voltage feedback, factory-programmed or adjustable in the field
AccessoriesA variety of options for mounting and commissioning

Features

Options for Demanding ApplicationsRotary, linear, and quick-running models are available for challenging installations.
Energy Savings and LongevityThe patented motor and ASIC combination lowers energy consumption and extends actuator life.
Stall ProtectionThe ASIC-controlled motor guards against stalling.
Smaller Transformer SizingLower power draw allows for smaller transformers.
Multi-Function TechnologyMFT models offer many proportional control functions and DC voltage feedback signals, set at the factory or tuned in the field.
Brownout ride-throughElectronic fail-safe models let you set a fail position that delays needless actuator movement during short brownouts, which prevents disruptions to the HVAC system and building automation system (BAS).
Overload protectionElectronic protection against overload extends actuator life and reduces maintenance costs.
Industry-standard compatibilityControl types work with common standards such as analog, BACnet MS/TP, and Modbus RTU.
Accessory flexibilityAccessories add mounting and commissioning options across applications.

Understanding the Fail-Safe Model Number

Fail safe diagram

Example Belimo Mechanical Fail Safe Damper Actuator Model Number

EFX24-MFT-SN4

Belimo Mechanical Fail-Safe Damper Actuator Model Number Key

Torque RatingSpeed✝VersionPower RequiredControlOptions
EF = 270 in-lbC = Fast RunningB = Basic24 = AC/DC 24 VBlank = On/Off-S = Built-in
Auxiliary Switch
US
AF = 180 in-lbL = Low NoiseX = Customized120 = AC 120 V*-3 = Floating PointEF…Series
NF = 90 in-lbBlank = Normal SpeedBlank = None230 = AC 230 V-SR = 2…10 VN4♦︎ = NEMA 4/4X
LF = 35 in-lbUP = AC 24…240 V**-PC = Phasecut (0.5…20 V)X…N4 Types
TF = 22 in-lb-ECON-RO3 = 3k W NTC Type 10 ThermistorH = Heater Option
-MFT = Multi-Function Technology
-MFT95 = 0…135 Ω
-MFT-20 = 6…9 V, 20 V Power Supply
-IP = BACnet/IP, Modbus TCP
-MOD = BACnet MS/TP, Modbus RTU

♦︎ NEMA 4 option on select models.
✝ Only available on certain LF and TF models.
*EF and TF series have AC 100…240 V nominal power supply.
**DC 24…125 V.

Example Belimo Electronic Fail Safe Damper Actuator Model Number

NKQX24-MFT

Belimo Electronic Fail-Safe Damper Actuator Model Number Key

Torque RatingSpeedVersionPower RequiredControlOptions
PK = 1400 in-lbQ = Quick RunningB = Basic24 = AC/DC 24 V*-1 = On/Off -T = Terminal Block
GK = 360 in-lb Blank = Normal SpeedX = CustomizedUP = AC 24…240 V**-3 = On/Off, Floating PointN4♦︎ = NEMA 4/4X
NK = 54 in-lb-SR = 2…10 VX…N4 Types
AHK = 100 lbf-MFT = Multi-Function TechnologyY = Heater Option
-IP = BACnet/IP, Modbus TCP
-MOD = BACnet MS/TP, Modbus RTU

♦︎ NEMA 4 option on select models.
*GK..24-3 is AC 24 V only.
**DC 24…125 V

Fire and Smoke Damper Actuators

The fire and smoke line includes four torque ratings (18, 30, 70, and 180 in-lb), 24 V, 120 V, and 230 V power options, built-in auxiliary switches, and a modulating fail-safe model at 180 in-lb. Linkage kits are available for indirect mounting and pneumatic retrofit projects. These actuators can be controlled from a central location and integrated into building safety systems, which supports smoke control that lets occupants exit and firefighters enter.

Specifications

ApplicationsFire dampers, smoke dampers, and combination fire and smoke dampers in ventilation and air-conditioning systems
Torque range18 in-lb to 180 in-lb at 350°F
Code complianceMeets all U.S. codes for commercial buildings
UL certificationPasses UL 555 and UL 555S at 350°F
Cycle testingTested for 30,000 open-closed cycles with approved dampers, exceeding UL’s 20,000-cycle requirement at damper static load
Quality controlISO 9001 certified
Warranty5 years

Features

Efficient microcontroller-driven motorsBelimo’s microcontrollers let the motors produce high torque at low current draw, and they run cooler, which extends service life
Reliable operation and supportISO 9001 certified quality control and a 5-year warranty back the actuators with dependable performance and strong customer support
Central control and safety system integrationActuators can be operated from a central location and tied into safety systems, helping keep the environment relatively smoke-free so occupants can exit efficiently and firefighters can enter
Life safety complianceCompliant with Life Safety Codes and Standards
Maximum safetyDesigned to meet code requirements in all situations, with cycle testing that surpasses the UL minimum

Understanding the Fire and Smoke Model Number

Fire and smoke diagram

Example Belimo Fire and Smoke Damper Actuator Model Number

FSNF24-S

Belimo Fire and Smoke Damper Actuator Model Number Key

Fire and SmokeTorque RatingActuator TypePower SupplyGenerationControlOptions
FS = Fire and SmokeA = 180 in-lbF = Fail-Safe24 = AC/DC 24 V*Blank = Original Blank = On/Off -S = Built-in Auxiliary Switches
N = 70 in-lbFB = Fail-Safe, Modulating (180 in-lb only)
120 = AC 120 V*

A = New Generation On/Off 
-SR = 2…10 V*
L = 30 in-lb230 = AC 230 V
AHK = 100 lbf
T = 18 in-lb

* Available with FSAFB24-SR & FSAFB24-SR-S only.

Quick Comparison

CategoryTorque rangeTypical useNotable features
Non fail-safe9–1,400 in-lbAir handlers, VAV, fan coil, unit ventilatorsMFT, adjustable end stops, quick-running options
Airflow measurement and control18–90 in-lb (rotary and in-duct), 34 lbf (linear)CAV and VAV systemsIntegrated pressure sensor, pressure independent, NFC
Fail-safe22–1,400 in-lbApplications requiring a defined position on power lossSuper capacitor, fail position options, overload protection
Fire and smoke18–180 in-lb at 350°FFire, smoke, and combination dampersUL 555/555S, 30,000-cycle testing, auxiliary switches

How to Choose the Right Damper Actuator

Whether you’re specifying actuators for a new build or replacing one that has failed or gone out of production, the selection process is the same. If you’re retrofitting, start by locating the part number and model on the existing actuator’s nameplate or in the old equipment manuals. That tells you what the unit does today, and most of the questions below can be answered from it. For more on that scenario, see our guide to selecting an actuator for a retrofit.

Work through these questions before specifying a model:

  1. What torque does the damper require?
    Size the actuator to the damper’s torque requirement. Quick-running versions have a slightly lower torque rating, so factor that in if speed matters.
  2. Is fail-safe actuation required?
    If the damper needs a defined position on power loss, specify a fail-safe actuator. If the application is code-driven fire or smoke protection, specify a listed fire and smoke actuator. On a retrofit, check whether the original unit was spring return or fail-safe, and match it.
  3. Is airflow measurement needed at the damper?
    Pressure independent airflow actuators can remove the manual balancing step.
  4. What control signal does the BAS use?
    Match the actuator to on/off, floating point, 2-10 V, MFT, BACnet, or Modbus. A new actuator has to speak the same language as your control system, so confirm compatibility before you order.
  5. What supply voltage is available?
    Options include 24 V AC/DC, 120 V, 230 V, and universal power supply on select models. In a retrofit, the voltage already at the damper often decides this for you.
  6. Can you direct couple to the damper shaft?
    Belimo actuators mount directly on standard damper shafts or jackshafts. Confirm the shaft size and type, and note that accessories can add mounting and commissioning options when the fit isn’t straightforward.
  7. What is the installation environment?
    Outdoor, high-humidity, and low-temperature locations may call for NEMA 4/4X housings or the heater option.

Frequently Asked Questions

What torque range do Belimo damper actuators cover?

The line covers 9 to 1,400 in-lb across rotary and linear models, suited to damper sizes as small as 4-inch round.

What is the difference between fail-safe and non fail-safe actuators?

Fail-safe actuators move the damper to a set position when power is lost. Non fail-safe actuators stay in their last position.

Which Belimo actuators communicate with a building automation system?

Select models in each category communicate over BACnet, Modbus, or MP-Bus, and select models add NFC for commissioning.

What warranty applies to Belimo damper actuators?

Belimo provides a 5-year warranty.

Are there actuators rated for outdoor or extreme conditions?

Yes. Select models have NEMA 4 and 4X housings with UV protection, and a heater option supports high-humidity and -40°F applications.

Need Help Choosing the Correct Actuator?

Belimo model numbers follow a consistent code covering torque rating, speed, version, power requirement, control type, and options. Matching each position of the code to your project requirements narrows the selection quickly. Contact us for assistance with specifying the correct model for your project.

Lock

Unlock Exclusive Pricing

Create your free account to unlock the best Belimo pricing on the internet with exclusive shipping rates on every order.

Recent News

×