- Flow characteristic
- modified equal percentage
- Leakage rate
- ANSI Class VI
- Housing
- bronze
- Seat
- 316 stainless steel
- Body Pressure Rating
- ANSI Class 250, up to 400 psi below 150°F
- Pipe connection
- NPT female ends
- Valve Size
- 0.5" [15]
- Pricing Variant
- G215S-F
- Pressure independent
- NO
- Product family
- Globe Valve
- Flow Pattern
- 2-way
- Valve Body Series
- G2..
- Non-Spring
- LVB(X)
- Spring
- LF
- Controllable flow range
- stem up - open A – AB
- ANSI Class
- 250
- Cv
- 1.3
- Maximum Inlet Pressure (Steam)
- 100 psi [690 kPa]
- Max Differential Pressure (water)
- 50 psi (345 kPa)
- Max Differential Pressure (Steam)
- 50 psi [345 kPa]
- Closing element
- 316 stainless steel
- Rangeability Sv
- 100:1
- Stem
- stainless steel AISI 316
- Stem seal
- EPDM O-ring
- Electronic fail-safe
- LVKB(X)
- Synonyms
- G215SF, G215S F, G215 S F
- Valve Trim
- Stainless steel
- Flow Characteristic Type
- modified equal percentage
- Unit of Measure
- PC
- DN
- 1/2"
- Pipe connection type
- internal thread
- Body pressure rating note
- up to 400 psi below 150°F
- Media Temp Range (water)
- 20...338°F [-7...170°C]
- Media Temperature Range (Steam)
- 32...338°F [0...170°C]
- cv range [gpm]
- 1.21...3.5
- kvs range [m³/h]
- 1.1...3.0
- Application
- This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include unit ventilators, VAV box re-heat coils and bypass loops. This valve is suitable for use in hydronic systems with variable flow. Bronze and stainless steel trim valves can be used for steam applications, depending on actuator and close-off combinations.
- Piping
- The valves should be mounted in a weather-protected area in a location that is within the ambient limits of the actuator. Allow sufficient room for valve with actuator and for service. The G2 and G3 preferred mounting position of the valve is with the valve stem vertical above the valve body, for maximum life. However, the assemblies can be mounted with the valve stem vertical or horizontal in relation to the pipe. The actuators should never be mounted underneath the valve, as condensation can build up and result in a failure of the actuators.
- CP65 Warning
- ⚠ WARNING: For Belimo Products sold in California, these Products do or may contain chemicals which are known to the State of California to cause cancer and or birth defects or other reproductive harms. For more information see www.p65warnings.ca.gov.
Datasheet Download: Datasheet
Need Help?
Call one of our experts 1-888-423-2525
Monday-Friday EST 6:00am - 4:00pm