F6150-300SHP+GW13
This product is no longer available. Please see our other products in this category or contact us for more info.
Butterfly Valve, 2-way, ANSI Class 300, DN 150, flange, Cv 1041
Weight | 42 lbs |
---|---|
Valve size | 6" [150] |
Brand | Belimo |
Pattern | 2-way |
Fluid | chilled or hot water, up to 60% glycol, steam |
ANSI Class | 300 |
- Close-Off Pressure
- 740 psi
- Flow characteristic
- modified equal percentage, unidirectional
- Housing
- carbon steel full lug (ASME B16.34)
- Stem
- 17-4 PH stainless steel
- Seat
- RPTFE
- Rangeability Sv
- 100:1
- Controllable flow range
- quarter turn, mechanically limited
- ANSI Class
- 300
- Maximum Velocity
- 32 FPS
- Pipe connection
- ASME/ANSI class 300 flange
- Bearing
- glass backed PTFE
- Disc
- 316 stainless steel
- Gland Seal
- TFE
- Valve Size
- 6" [150]
- Gear operator materials
- Gears - hardened steel
- Lug threads
- 3/4-10 UNC
- Number of Bolt Holes
- 12
- BFV flange type
- Lug types
- Flow Rating
- 2820
- Cv
- 1041
- Pressure independent
- NO
- Media Temp Range (water)
- -22...400°F [-30...204°C]
- Safety notes
- Cable for ZIP-RS232 US and ZIP-USB-MP US to Belimo gateways. Battery Back Up System for SY(7~10)-110 Weather shield - galvaneal 13x8x6" (LxWxD). Cable for ZTH US to diagnostic/programming socket. Cable for ZTH US to actuators w/o diagnostics socket. 50% voltage divider kit (resistors with wires). PC Tool computer programming interface, serial port. 3/4" shaft adaptor for ZS-300(-5). Battery Back Up System for SY(8~12)-110P 1/2" shaft adaptor, standard wtih ZS-300(-5).
- Application
- 1. Valves are rated at 725 psi differential pressure in the closed position @100°F media temperature. 2. Valves are furnished with lugs tapped for use between ANSI Class 250/300 flanges conforming to ANSI B16.5 Standards. 3. 2-Way assemblies are furnished assembled, calibrated and tested, ready for installation. 4. Dimension "D" allows for actuator(s) removal without the need to remove the valve from the pipe. 5. Weather shields are available, dimensional data upon request. 6. Dual actuated valves have actuators mounted on a single common shaft. 7. Flange gaskets (2 required, not provided with valve) MUST be used between valve and ANSI flange. 8. Flange bolts are not included with the valve. These are furnished by others.
Datasheet Download: Datasheet
Installation instructions Download: Installation instructions
Need Help?
Call one of our experts 1-888-423-2525
Monday-Friday EST 6:00am - 4:00pm