- Ambient temperature
- -40...158°F [-40...70°C]
- Operation
- The ZIP Economizer ™ Energy Module has full functionality when connected to the ECON-ZIP-Base. With its unique keyed slot, it makes installation a breeze.
- Product Features
- Auto-detection of inputted devices and non-proprietary sensors
- Non-operating temperature
- -40...176°F [-40...80°C]
- Ambient humidity
- 5...95% r.H. non-condensing
- Agency Listing
- EMC according to UL60730-1
- Connectors
- 1/4" male spade connectors
- Housing material
- UL94-5V
- Nominal voltage
- AC
- Environmental
- RoHS, Conformally coated
- Rated Impulse Voltage
- 800V
- Supported CO2 Sensor
- 0-10 VDC, Sensor auto-detection
- Auxiliary Input - Remote Potentiometer
- 2-10VDC
- Auxiliary Input - Purge Contact
- On/Off - 24 VAC, 50/60HZ - Current Load min 10mA
- Indoor Fan Speed Selection
- 100'000 cycles @ inrush current of 3.5A, normal current 1.5A Impedance for Auto detection @ 24V: <600Ohm @ 60Hz, <800Ohm @ 50Hz
- Exhaust Fan Selection
- 100'000 cycles @ inrush current of 3.5A, normal current 1.5A, Impedance for Auto detection @ 24V: <600Ohm @ 60Hz, <800Ohm @ 50Hz
- Product family
- Economizer
- Application
- The ZIP Economizer™ Energy Module provides additional I/Os to offer higher control functionalities that will save energy and will meet new and future minimum code requirements. The Energy Module is needed for CO2 sensors, Indoor Fan, 2 Speed Fan, Exhaust Fan, Remote Potentiometer for Damper Positioning, as well as purge control. The auto-detection and plug and play capability offers quick set up.