22WDP-532

$481.95

Each
Differential Pressure Sensor Water, 0...30 psi, active, 4...20 mA

or sign up for a free membership to get our lowest pricing.

Weight 1.2 lbs
Application

Pipe

Brand

Belimo

Sensor type

pressure

Output signal

4…20 mA

Medium temperature
15...175°F [-10...80°C]
Ambient temperature
15...120°F [-10...50°C]
Output signal active note
current output: max. 900 Ω load
Power supply DC
15...24 V
Power supply tolerance DC
±10%
Power consumption DC
0.5 W
Measuring values
differential pressure
Sensor type
pressure
Application
Pipe
Cable entry
angle plug according to DIN 43650, construction A
Electrical connection
Connector Plug for wire 0.5...1.5 mm²
Ambient humidity
max. 95% r.H. non-condensing
Mounting
installation position unrestricted
Mounting instruction
Mounting instruction - 71937-00001B 22WDP
Degree of protection IEC/EN
IP65
Degree of protection NEMA/UL
NEMA 4
Degree of Protection
IP65, NEMA 4
Certification IEC/EN
IEC/EN 60730-1
Protection class IEC/EN
III protective extra-low voltage (pelv)
Protection class UL
UL Class 2 Supply
Quality Standard
ISO 9001
Material short text
Water Diff Pressure Sensor 30psi A
Output signal
4...20 mA
Housing
base: stainless steel 1.4305|cover: aluminum pressure die casting
Optional accessories
A-22WP-A03|A-22WP-A05|A-22WP-A07|A-22WP-A09
Electrical connection note
for wire 0.5...1.5 mm²
Connection
Connector Plug
Product family
Sensor
CAD data 3D
Belimo_22WDP-132_3D.dwg|Belimo_22WDP-132_3D.dxf|Belimo_22WDP-132_3D.igs|Belimo_22WDP-132_3D.sat|Belimo_22WDP-132_3D.stp
Measuring range rel. pressure
0...30 psi
Accuracy pressure
<±1% of measuring range @ 23...167°F [-5...75°C]
Measuring media
air and non-aggressive gases
Mechanical connection
pressure connector: 1/4" NPT
Housing seal
EPDM
Medium wetted parts
stainless steel 1.4301, ceramic
Dynamic response
Suitable for static and dynamic measurements. Response time: <10ms
Maximum System pressure
300 psi
Overpressure range
85 psi
Overpressure range note
Single-sided
Output signal active pressure
4...20 mA
Application text
Active sensor (4 to 20 mA) for measuring the differential pressure in liquid or dry media. Various pressure ranges, rugged NEMA 4 / IP65 and compact stainless steel housing. Optional stainless steel or brass pipe connection adapters also available.
General caution
The installation and assembly of electrical equipment should only be performed by authorized personnel. This device has been designed for use in stationary heating, ventilation and air conditioning systems and must not be used outside the specified field of application. Unauthorised modifications are prohibited. The product must not be used in relation with any equipment that in case of a failure may threaten human, animals or assets. Ensure all power is disconnected before installing. Do not connect to live/operating equipment.
Additional caution
Please comply with • Local laws, health & safety regulations, technical standards and regulations • Condition of the device at the time of installation, to ensure safe installation • This data sheet and installation manual

Installation instructions Download: Installation instructions