- Measuring range temperature active note
- Active sensor: range selectable|Attention: max. measuring temperature is restricted by max. medium temperature (see Safety data)
- Jumper setting note
- the adjustment of the measuring ranges is made by changing the bonding jumpers|the output value in the new measuring range is available after 2 seconds
- Accuracy temperature active
- ±0.9°F @ 70°F [±0.5°C @ 21°C]
- Cable gland
- PA6, black
- Medium temperature
- -30...160°F [-35...70°C]
- Ambient temperature
- -30...120°F [-35...50°C]
- Output signal active temperature
- DC 0...5 V|DC 0...10 V
- Output signal active note
- output DC 0...5/10 V with jumper adjustable|voltage output: min. 5 kΩ load
- Power supply DC
- 15...24 V
- Power supply tolerance DC
- ±10%
- Power consumption DC
- 0.42 W
- Power supply AC
- 24 V
- Power supply tolerance AC
- ±10%
- Power consumption AC
- 0.84 VA
- Measuring values
- temperature
- Sensor type
- temperature
- Housing type
- Surface
- Application
- Pipe
- Sensor powertype
- active
- Cable entry
- Cable gland with strain relief Ø6...8 mm (1/2" NPT conduit adapter included)
- Electrical connection
- Removable spring loaded terminal block max. 2.5 mm²
- Ambient humidity
- max. 95% r.H. non-condensing
- Scope of delivery
- 1/2" NPT conduit adapter
- Mounting instruction
- 01HT, 22HT US Mounting Instruction Sheet
- Degree of protection IEC/EN
- IP65
- Degree of protection NEMA/UL
- NEMA 4X
- Degree of Protection
- IP65, NEMA 4X
- Certification IEC/EN
- IEC/EN 60730-1
- Certification UL
- cULus acc. to UL60730-1A/-2-9, CAN/CSA E60730-1:02/-2-9
- Protection class IEC/EN
- III protective extra-low voltage (pelv)
- Protection class UL
- UL Class 2 Supply
- Quality Standard
- ISO 9001
- Material short text
- Housing Contact Temp Sensor V
- Output signal
- DC 0...5 V DC 0...10 V
- Housing
- cover: lexan, orange|base: lexan, orange|seal: 0467 NBR70, black
- Multirange
- 8 fields selectable
- Optional accessories
- A-22P-A40|A-22P-A42|A-22P-A44
- Electrical connection note
- Removable spring loaded terminal block max. 2.5 mm²
- Connection
- terminals
- Product family
- Sensor
- CAD data 3D
- Belimo_22HT-12_3D.dwg|Belimo_22HT-12_3D.dxf|Belimo_22HT-12_3D.igs|Belimo_22HT-12_3D.sat|Belimo_22HT-12_3D.stp
- Setting range S0 [°C]
- -50...50°C
- Setting range S0 [°F]
- -30...130°F
- Setting range S1 [°C]
- -10...120°C
- Setting range S1 [°F]
- 0...250°F
- Setting range S2 [°C]
- 0...50°C
- Setting range S2 [°F]
- 40...140°F
- Setting range S3 [°C]
- 0...250°C
- Setting range S3 [°F]
- 30...480°F
- Setting range S4 [°C]
- -15...35°C
- Setting range S4 [°F]
- 0...100°F
- Setting range S5 [°C]
- 0...100°C
- Setting range S5 [°F]
- 40...240°F
- Setting range S6 [°C]
- -20...80°C
- Setting range S6 [°F]
- 40...90°F
- Setting range S7 [°C]
- 0...160°C
- Setting range S7 [°F]
- 0...150°F
- Mounting type pipe
- Strap-on
- Housing surface temperature
- max. 160°F [70°C]
- Application text
- Active surface contact temperature sensor (0 to 5/10 V) for pipe applications. Spring loaded brass contact to ensure fast response and accurate readings. NEMA 4X / IP65 rated enclosure. [Pipe clamp included.]
- General caution
- The installation and assembly of electrical equipment should only be performed by authorized personnel. This device has been designed for use in stationary heating, ventilation and air conditioning systems and must not be used outside the specified field of application. Unauthorised modifications are prohibited. The product must not be used in relation with any equipment that in case of a failure may threaten human, animals or assets. Ensure all power is disconnected before installing. Do not connect to live/operating equipment.
- Additional caution
- Please comply with • Local laws, health & safety regulations, technical standards and regulations • Condition of the device at the time of installation, to ensure safe installation • This data sheet and installation manual
Datasheet Download: Datasheet
Installation instructions Download: Installation instructions
Need Help?
Call one of our experts 1-888-423-2525
Monday-Friday EST 6:00am - 4:00pm