- Cable gland
- PA6, black
- Medium temperature
- -5...140°F [-20...60°C]
- Ambient temperature
- -5...120°F [-20...50°C]
- Power supply DC
- 15...24 V
- Power supply tolerance DC
- ±10%
- Power consumption DC
- 0.8 W
- Power supply AC
- 24 V
- Power supply tolerance AC
- ±10%
- Power consumption AC
- 1.6 VA
- Display
- LED green - power supply ok red - dew permeation
- Display type
- LED
- Display note
- green - power supply ok|red - dew permeation
- Measuring values
- condensation
- Sensor type
- humidity
- Housing type
- Housing Surface
- Application
- Condensation
- Cable entry
- Cable gland with strain relief Ø6...8 mm (1/2" NPT conduit adapter included)
- Electrical connection
- Removable spring loaded terminal block max. 2.5 mm²
- Ambient humidity
- max. 95% r.H. non-condensing
- Scope of delivery
- Mounting plate|Cable tie|1/2" NPT conduit adapter
- Mounting instruction
- 22HH, 22HH-..X US Mounting Instruction Sheet
- Degree of protection IEC/EN
- IP65
- Degree of Protection
- IP65,
- Certification IEC/EN
- IEC/EN 60730-1
- Certification UL
- cULus acc. to UL60730-1A/-2-9/-2-13, CAN/CSA E60730-1:02/-2-9
- Protection class IEC/EN
- III safety extra-low voltage (selv)
- Protection class UL
- UL Class 2 Supply
- Quality Standard
- ISO 9001
- Material short text
- Humidity Switch EXT
- Output signal
- switch
- Housing
- cover: lexan, orange|base: lexan, orange|seal: 0467 NBR70, black
- Optional accessories
- A-22P-A44
- Electrical connection note
- Removable spring loaded terminal block max. 2.5 mm²
- Connection
- terminals
- Product family
- Sensor
- CAD data 3D
- Belimo_22HH-100X_3D.dwg|Belimo_22HH-100X_3D.dxf|Belimo_22HH-100X_3D.igs|Belimo_22HH-100X_3D.sat|Belimo_22HH-100X_3D.stp
- Output signal switch note
- changeover contact, isolated; max. 24 V / 1.0 A (resistive)
- Cable length
- 6.5 ft. [2 m]
- Application text
- Condensation sensor with LED signal. Designed to provide a switched output signal to prevent condensation on chilled surfaces such as chilled beams. NEMA 4X / IP65 rated enclosure. Also available direct mounted and without 6 ft/2 m remote cable.
- General caution
- The installation and assembly of electrical equipment should only be performed by authorized personnel. This device has been designed for use in stationary heating, ventilation and air conditioning systems and must not be used outside the specified field of application. Unauthorised modifications are prohibited. The product must not be used in relation with any equipment that in case of a failure may threaten human, animals or assets. Ensure all power is disconnected before installing. Do not connect to live/operating equipment.
- Additional caution
- Please comply with • Local laws, health & safety regulations, technical standards and regulations • Condition of the device at the time of installation, to ensure safe installation • This data sheet and installation manual
Datasheet Download: Datasheet
Installation instructions Download: Installation instructions
Need Help?
Call one of our experts 1-888-423-2525
Monday-Friday EST 6:00am - 4:00pm