- Measuring range temperature
- -30...210°F [-35...100°C]
- Accuracy temperature passive
- passive sensors depending on used type Pt.. = ±0.5°F @ 32°F [±0.3°C @ 0°C] Ni.. = ±0.7°F @ 32°F [±0.4°C @ 0°C] NTC.. = ±0.3°F @ 77°F [±0.2°C @ 25°C]
- Medium temperature
- -30...210°F [-35...100°C]
- Ambient temperature
- -30...210°F [-35...100°C]
- Output signal passive temperature
- Pt1000|Ni1000 (JCI)|NTC10k2|NTC10k3|NTC20k
- Probe diameter
- 0.24" [6 mm]
- Application text
- Surface contact mounted temperature sensor for pipe and arched surfaces. Plenum rated cable and a brass probe for fast response and accuracy and NEMA 4 / IP65 rated. [Pipe clamp included.]
- Measuring values
- temperature
- Sensor type
- temperature
- Housing type
- Surface
- Application
- Pipe
- Sensor powertype
- passive
- Cable specification
- 1 pair shielded plenum cable, 22AWG tinned copper, green jacket, -40°F to 300°F (-40°C to 150°C), 300 V
- Electrical connection
- cable 6.5 ft. [2 m], 2-wire
- Ambient humidity
- max. 95% r.H. non-condensing
- Mounting instruction
- 01ST US Mounting Instruction Sheet
- Degree of protection IEC/EN
- IP65
- Degree of protection NEMA/UL
- NEMA 4
- Degree of Protection
- IP65, NEMA 4
- Certification IEC/EN
- IEC/EN 60730-1
- Certification UL
- cULus acc. to UL60730-1A/-2-9, CAN/CSA E60730-1:02/-2-9
- Protection class IEC/EN
- III safety extra-low voltage (selv)
- Protection class UL
- UL Class 2 Supply
- Quality Standard
- ISO 9001
- Material short text
- Contact Temp Sensor NTC10kP 2m
- Output signal
- NTC10K3
- Optional accessories
- A-22P-A40|A-22P-A42|A-22P-A44
- Electrical connection note
- 2-wire
- Connection
- cable
- Product family
- Sensor
- CAD data 3D
- Belimo_01ST-5..3_3D.stp
- Cable length
- 6.5 ft. [2 m]
- Mounting type pipe
- Strap-on
- General caution
- The installation and assembly of electrical equipment should only be performed by authorized personnel. This device has been designed for use in stationary heating, ventilation and air conditioning systems and must not be used outside the specified field of application. Unauthorised modifications are prohibited. The product must not be used in relation with any equipment that in case of a failure may threaten human, animals or assets. Ensure all power is disconnected before installing. Do not connect to live/operating equipment.
- Additional caution
- Please comply with • Local laws, health & safety regulations, technical standards and regulations • Condition of the device at the time of installation, to ensure safe installation • This data sheet and installation manual
Datasheet Download: Datasheet
Installation instructions Download: Installation instructions
Need Help?
Call one of our experts 1-888-423-2525
Monday-Friday EST 6:00am - 4:00pm