22DTM-56

$511.65

Each

Duct Sensor CO₂ / Humidity / Temperature active, BACnet, Probe length 7″ [180 mm], Probe diameter 0.78″ [19.5 mm]

or sign up for a free membership to get our lowest pricing.

Weight 0.62 lbs
Application

Duct

Brand

Belimo

Sensor type

air quality

Output signal

BACnet

Communicative
communicative
Communicative control
BACnet MS/TP
RS485 documentation
The separate document, BACnet PICS, informs about the PICS, MAC addressing and bus Termination (DIP1 & DIP2).
Measuring range temperature
30...120°F [0...50°C]
Measuring range temperature active note
selectable via BACnet|Attention: max. measuring temperature is restricted by max. medium temperature (see Safety data)
Accuracy temperature active
±0.9°F @ 70°F [±0.5°C @ 21°C]
Measuring range humidity
0...100% r.H.|selectable via BACnet
Measuring range CO₂
0...2000 ppm|selectable via BACnet
Accuracy humidity
±2% between 10 to 90% r.H. @ 70°F [21°C]
Accuracy CO₂
±(50 ppm + 3% of measuring value)
Operating condition air flow
min. 1 ft/s [0.3 m/s]|max. 33 ft/s [10 m/s]
Calibration
self-calibration, Dual Channel
Sensor Technology
CO₂: NDIR (non dispersive infrared) dual channel|r.H.: with stainless steel wire mesh filter
Cable gland
PA6, black
Medium temperature
30...120°F [0...50°C]
Ambient temperature
30...120°F [0...50°C]
Output signal active temperature
DC 0...5 V|DC 0...10 V
Output signal active CO₂
DC 0...5 V|DC 0...10 V
Output signal active note
Output DC 0...5/10 V selectable with switch
Probe material
PA6, black
Probe diameter
0.78" [19.5 mm]
Probe length
7" [180 mm]
Power supply DC
15...24 V
Power supply tolerance DC
±10%
Power consumption DC
0.3 W
Power supply AC
24 V
Power supply tolerance AC
±10%
Power consumption AC
6 VA
Build-up of self-heating remark
Remark: Occurring draft leads to a better carrying-off of dissipative power at the sensor. Thus temporally limited fluctuations might occur upon temperature measurement.
Mounting type duct
Single Point
Measuring range enthalpy
0...85 kJ/kg|selectable via BACnet
Measuring range dew point
0...200°F [-20...80°C]|selectable via BACnet
Measuring range absolute humidity
0...80 g/m³|selectable via BACnet
Application text
For combined measurement of CO₂, relative humidity and temperature in the duct. Dual channel CO₂ technology. The measured values are output via BACnet. NEMA 4X / IP65 rated enclosure.
Measuring values
CO₂|temperature|relative humidity
Sensor type
air quality
Housing type
Duct
Application
Duct
Sensor powertype
active
Communication
BACnet MS/TP
Cable entry
Cable gland with strain relief 2 x Ø6 mm (1/2" NPT conduit adapter included)
Electrical connection
Removable spring loaded terminal block max. 2.5 mm²
Ambient humidity
max. 95% r.H. non-condensing
Scope of delivery
1/2" NPT conduit adapter
Mounting instruction
22DTM US Mounting Instruction Sheet|Protocol Implementation Conformance Statement - Sensor BACnet
Degree of protection IEC/EN
IP65
Degree of Protection
IP65,
Certification IEC/EN
IEC/EN 60730-1
Certification UL
cULus acc. to UL60730-1A/-2-9/-2-13, CAN/CSA E60730-1:02/-2-9
Protection class IEC/EN
III safety extra-low voltage (selv)
Protection class UL
UL Class 2 Supply
Quality Standard
ISO 9001
Material short text
Duct CO2+Temp+Hum Sensor BAC
Output signal
BACnet
Housing
UV resistant|cover: lexan, orange|base: lexan, orange|seal: 0467 NBR70, black
Optional accessories
A-22D-A06|A-22G-A01.1|A-22G-A02.1
Electrical connection note
Removable spring loaded terminal block max. 2.5 mm²
Connection
terminals
Product family
Sensor
CAD data 3D
Belimo_22DTM-16_3D.dwg|Belimo_22DTM-16_3D.dxf|Belimo_22DTM-16_3D.igs|Belimo_22DTM-16_3D.sat|Belimo_22DTM-16_3D.stp
Notes box electrical installation
Connection via safety isolating transformer. Parallel power connection of additional devices possible. Observe the performance data. The wiring of the line for BACnet MS/TP / Modbus RTU is to be carried out in accordance with applicable RS485 regulations. Modbus / BACnet: Supply and communication are not galvanically isolated. Connect earth signal of the devices with one another.
General remarks sensors
Sensing devices with a transducer should always be operated in the middle of the measuring range to avoid deviations at the measuring end points. The ambient temperature of the transducer electronics should be kept constant. The transducers must be operated at a constant supply voltage (±0.2 V). When switching the supply voltage on/off, onsite power surges must be avoided.
Application notice humidity sensors
Refrain from touching the sensitive humidity sensor/element. Touching the sensitive surface will void warranty. For standard environmental conditions the manufacturing accuracy specified in the datasheet will be covered by the calibration warranty for two years. When exposed to harsh environmental conditions such as; high ambient temperature and/or high levels of humidity or presence of aggressive gases (i.e. chlorine, ozone, ammonia) the sensor element may be affected and readings may be outside specified accuracy. Replacement of deteriorated humidity sensor due to harsh environmental conditions are not subject of the general warranty.
Information self-calibration feature CO₂
All CO₂ sensors are subject to drift caused by the aging process of the components, resulting in regular re-calibration or replacement units. However the dual channel technology integrates automatic self-calibration technology vs common used ABC-Logic sensors. Dual channel self-calibration technology is ideally suited for applications operating 24/7 hours such as hosiptals or other commerical applications. Manual calibration is not required.
Build-up of self-heating
Temperature sensors with electronic components always have a dissipative power which affects the temperature measurement of the ambient air. The dissipation in active temperature sensors shows a linear increase with rising operating voltage. This dissipative power should be taken into account when measuring temperature. As Belimo transducers work with a variable operating voltage, only one operating voltage can be taken into consideration, for reasons of production engineering. Transducers 0 to 10 V / 4 to 20 mA have a standard setting at an operating voltage of DC 24 V. That means, that at this voltage, the expected measuring error of the output signal will be the least. For other operating voltages, the offset error will be increased by a changing power loss of the sensor electronics. If a re-calibration should become necessary later directly on the sensor, this can be done by means of a trimming potentiometer on the sensor board.
General caution
The installation and assembly of electrical equipment should only be performed by authorized personnel. This device has been designed for use in stationary heating, ventilation and air conditioning systems and must not be used outside the specified field of application. Unauthorised modifications are prohibited. The product must not be used in relation with any equipment that in case of a failure may threaten human, animals or assets. Ensure all power is disconnected before installing. Do not connect to live/operating equipment.
Additional caution
Please comply with • Local laws, health & safety regulations, technical standards and regulations • Condition of the device at the time of installation, to ensure safe installation • This data sheet and installation manual

Installation instructions Download: Installation instructions