- Measuring range temperature active note
- Active sensor: range selectable|Attention: max. measuring temperature is restricted by max. medium temperature (see Safety data)
- Jumper setting note
- the adjustment of the measuring ranges is made by changing the bonding jumpers|the output value in the new measuring range is available after 2 seconds
- Accuracy temperature active
- ±0.9°F @ 70°F [±0.5°C @ 21°C]
- Cable gland
- PA6, black
- Medium temperature
- -60...245°F [-50...120°C]
- Ambient temperature
- -30...120°F [-35...50°C]
- Output signal active temperature
- 4...20 mA
- Output signal active note
- current output: max. 500 Ω load
- Probe diameter
- 0.24" [6 mm]
- Probe length
- 2" [50 mm]
- Power supply DC
- 15...24 V
- Power supply tolerance DC
- ±10%
- Power consumption DC
- 0.5 W
- Build-up of self-heating remark
- Remark: Occurring draft leads to a better carrying-off of dissipative power at the sensor. Thus temporally limited fluctuations might occur upon temperature measurement.
- Application text
- Active sensor (4 to 20 mA) for measuring the temperature in pipe and air applications. Incorporates a stainless steel probe and plenum rated cable.
- Measuring values
- temperature
- Sensor type
- temperature
- Housing type
- Housing Surface
- Application
- Cable
- Sensor powertype
- active
- Cable entry
- Cable gland with strain relief Ø6...8 mm (1/2" NPT conduit adapter included)
- Cable specification
- 1 pair shielded plenum cable, 22AWG tinned copper, green jacket, -40°F to 300°F (-40°C to 150°C), 300 V
- Electrical connection
- Removable spring loaded terminal block max. 2.5 mm²
- Ambient humidity
- max. 95% r.H. non-condensing
- Scope of delivery
- Mounting plate|Dowel|Screws|1/2" NPT conduit adapter
- Mounting instruction
- Mounting instruction - 71956-00001.E 22CT-..
- Degree of protection IEC/EN
- IP65
- Degree of Protection
- IP65,
- Certification IEC/EN
- IEC/EN 60730-1
- Certification UL
- cULus acc. to UL60730-1A/-2-9, CAN/CSA E60730-1:02/-2-9
- Protection class IEC/EN
- III protective extra-low voltage (pelv)
- Protection class UL
- UL Class 2 Supply
- Quality Standard
- ISO 9001
- Material short text
- Cable Temp Sensor 50x6 2m A MULT
- Output signal
- 4...20 mA
- Housing
- cover: lexan, orange|base: lexan, orange|seal: 0467 NBR70, black
- Multirange
- 8 fields selectable
- Recommended accessories water
- A-22P-A05|A-22P-A17|A-22P-A36|A-22P-A07|A-22P-A19|A-22P-A37|A-22P-A09|A-22P-A21|A-22P-A38|A-22P-A11|A-22P-A23|A-22P-A39|A-22P-A13|A-22P-A25|A-22P-A15|A-22P-A27|A-22P-A44|A-22P-A45
- Electrical connection note
- Removable spring loaded terminal block max. 2.5 mm²
- Connection
- terminals
- Product family
- Sensor
- CAD data 3D
- Belimo_22CT-14H_3D.dwg|Belimo_22CT-14H_3D.dxf|Belimo_22CT-14H_3D.igs|Belimo_22CT-14H_3D.sat|Belimo_22CT-14H_3D.stp
- Cable length
- 6.5 ft. [2 m]
- Setting range S0 [°C]
- -50...50°C
- Setting range S0 [°F]
- -30...130°F
- Setting range S1 [°C]
- -10...120°C
- Setting range S1 [°F]
- 0...250°F
- Setting range S2 [°C]
- 0...50°C
- Setting range S2 [°F]
- 40...140°F
- Setting range S3 [°C]
- 0...250°C
- Setting range S3 [°F]
- 30...480°F
- Setting range S4 [°C]
- -15...35°C
- Setting range S4 [°F]
- 0...100°F
- Setting range S5 [°C]
- 0...100°C
- Setting range S5 [°F]
- 40...240°F
- Setting range S6 [°C]
- -20...80°C
- Setting range S6 [°F]
- 40...90°F
- Setting range S7 [°C]
- 0...160°C
- Setting range S7 [°F]
- 0...150°F
- Housing surface temperature
- max. 160°F [70°C]
- SI Protection
- YES
- Optional accessories air
- A-22D-A03|A-22D-A05
- General caution
- The installation and assembly of electrical equipment should only be performed by authorized personnel. This device has been designed for use in stationary heating, ventilation and air conditioning systems and must not be used outside the specified field of application. Unauthorised modifications are prohibited. The product must not be used in relation with any equipment that in case of a failure may threaten human, animals or assets. Ensure all power is disconnected before installing. Do not connect to live/operating equipment.
- Additional caution
- Please comply with • Local laws, health & safety regulations, technical standards and regulations • Condition of the device at the time of installation, to ensure safe installation • This data sheet and installation manual
Datasheet Download: Datasheet
Installation instructions Download: Installation instructions
Need Help?
Call one of our experts 1-888-423-2525
Monday-Friday EST 6:00am - 4:00pm