01CT-5ML
$18.00
EachCable Temperature Sensor with mounting flange passive, NTC10K3, Probe diameter 0.24″ [6 mm], cable 6.5 ft. [2 m], 2-wire
Weight | 0.15 lbs |
---|---|
Application | Cable |
Brand | Belimo |
Sensor type | temperature |
Output signal | NTC10K3 |
- Measuring range temperature
- -30...210°F [-35...100°C]
- Accuracy temperature passive
- passive sensors depending on used type Pt.. = ±0.5°F @ 32°F [±0.3°C @ 0°C] NTC.. = ±0.3°F @ 77°F [±0.2°C @ 25°C]
- Medium temperature
- -30...210°F [-35...100°C]
- Ambient temperature
- -30...210°F [-35...100°C]
- Output signal passive temperature
- Pt1000|NTC10k2|NTC10k3|NTC20k
- Probe diameter
- 0.24" [6 mm]
- Probe length
- 4" [100 mm]
- Application text
- Cable type temperature sensor with adjustable rubber mounting flange for measuring temperature in FCU, AHU and VAV applications. Incorporates a stainless steel probe and plenum rated cable.
- Measuring values
- temperature
- Sensor type
- temperature
- Housing type
- Cable
- Application
- Cable
- Sensor powertype
- passive
- Cable specification
- 1 pair shielded plenum cable, 22AWG tinned copper, green jacket, -40°F to 300°F (-40°C to 150°C), 300 V
- Electrical connection
- cable 6.5 ft. [2 m], 2-wire
- Ambient humidity
- max. 95% r.H. non-condensing
- Scope of delivery
- mounting flange
- Mounting instruction
- Installation instruction - 71998-00001.B - 01CT-F _01CT-L-P
- Degree of protection IEC/EN
- IP67
- Degree of protection NEMA/UL
- NEMA 4X
- Degree of Protection
- IP67, NEMA 4X
- Certification IEC/EN
- IEC/EN 60730-1
- Certification UL
- cULus acc. to UL60730-1A/-2-9, CAN/CSA E60730-1:02/-2-9
- Protection class IEC/EN
- III safety extra-low voltage (selv)
- Protection class UL
- UL Class 2 Supply
- Quality Standard
- ISO 9001
- Material short text
- Cable Temp Sensor NTC10kP 100x6 2m
- Output signal
- NTC10K3
- Electrical connection note
- 2-wire
- Connection
- cable
- Product family
- Sensor
- CAD data 3D
- Belimo_01CT-5..L-P_3D.stp
- Cable length
- 6.5 ft. [2 m]
- SI Protection
- YES
- General caution
- The installation and assembly of electrical equipment should only be performed by authorized personnel. This device has been designed for use in stationary heating, ventilation and air conditioning systems and must not be used outside the specified field of application. Unauthorised modifications are prohibited. The product must not be used in relation with any equipment that in case of a failure may threaten human, animals or assets. Ensure all power is disconnected before installing. Do not connect to live/operating equipment.
- Additional caution
- Please comply with • Local laws, health & safety regulations, technical standards and regulations • Condition of the device at the time of installation, to ensure safe installation • This data sheet and installation manual
Datasheet Download: Datasheet
Need Help?
Call one of our experts 1-888-423-2525
Monday-Friday EST 6:00am - 4:00pm