01APS-504

$41.40

Each

Differential Pressure Switch, 2.00…10.00 inch WC [500…2500 Pa], passive, switch

Also available in bulk, increments of 45 units

or sign up for a free membership to get our lowest pricing.

Weight 0.26 lbs
Application

Duct

Brand

Belimo

Sensor type

pressure

Output signal

switch

Medium temperature
-5...140°F [-20...60°C]
Ambient temperature
-5...140°F [-20...60°C]
Mounting type duct
Single Point
Measuring values
differential pressure
Sensor type
pressure
Housing type
Duct
Application
Duct
Sensor powertype
passive
Non-operating temperature
-40...185°F [-40...85°C]
Cable entry
Cable gland with strain relief Ø6...8 mm (1/2" NPT conduit adapter included)
Electrical connection
terminals for wire 0.5...1.5 mm²
Ambient humidity
max. 95% r.H. non-condensing
Scope of delivery
PVC tube 2 m|2 x Duct connectors (plastic)
Mounting instruction
01APS US Mounting Instruction Sheet
Degree of protection IEC/EN
IP54
Degree of protection NEMA/UL
NEMA 3
Degree of Protection
IP54, NEMA 3
Certification IEC/EN
IEC/EN 60730-1
Certification UL
ETL listed, UL508, CSA C22.2 No.14
Quality Standard
ISO 9001
Material short text
Diff Air Pressure Switch 2..10 "wc
Output signal
switch
Housing
base: PA 6.6|cover: ps
Electrical connection note
for wire 0.5...1.5 mm²
Connection
terminals
Product family
Sensor
CAD data 3D
Belimo_01APS-104_3D.dwg|Belimo_01APS-104_3D.dxf|Belimo_01APS-104_3D.igs|Belimo_01APS-104_3D.sat|Belimo_01APS-104_3D.stp
Measuring range diff. pressure
2.00...10.00 inch WC
Accuracy pressure
±15% (tolerance for upper and lower switching pressure)
Burst pressure
10 kPa / 40 inch WC
Measuring media
air, non-combustible and non-aggressive gases
Overpressure range
10 kPa / 40 inch WC
Output signal pressure switch
changeover
Output signal switch note
contact current max. 1.0 A (0.4) / AC 250 V
Output signal pressure switch note
contact current max. 1.0 A (0.4) / AC 250 V
Application text
For monitoring overpressure, vacuum and differential pressure of air or other non-combustible, non-aggressive gases for both HVAC and energy management applications. Automatic reset and field adjustable setpoints and switching hysteresis.
General caution
The installation and assembly of electrical equipment should only be performed by authorized personnel. This device has been designed for use in stationary heating, ventilation and air conditioning systems and must not be used outside the specified field of application. Unauthorised modifications are prohibited. The product must not be used in relation with any equipment that in case of a failure may threaten human, animals or assets. Ensure all power is disconnected before installing. Do not connect to live/operating equipment.
Additional caution
Please comply with • Local laws, health & safety regulations, technical standards and regulations • Condition of the device at the time of installation, to ensure safe installation • This data sheet and installation manual

Installation instructions Download: Installation instructions