GKX24-MFT-X1

This product is no longer available. Please see our other products in this category or contact us for more info.

Valve Actuator,Electronic Fail-Safe,24V,MFT

Weight 4.0 lbs
Actuator Type

Electronic fail-safe

Brand

Belimo

Control type

MFT/Programmable

Maintenance
maintenance free
Power consumption in operation
12 W
Power consumption in rest position
3 W
Transformer sizing
21 VA (class 2 power source)
Ambient humidity
5...95% r.H. non condensing (EN 60730-1)
Housing material
UL94-5VA
Electrical Connection
18 GA plenum cable with 1/2" conduit connector, degree of protection NEMA 2 / IP54, 3 ft [1 m] 10 ft [3 m] and 16ft [5 m]
Manual override
external push button
Angle of rotation
Max. 95°, adjustable with mechanical stop
Noise level, motor
<45 dB (A) 
Position indication
reflective visual indicator (snap on)
Ambient temperature
-22...122°F [-30...50°C]
Non-operating temperature
-40...176°F [-40...80°C]
Control
MFT/programmable
direction of rotation motor
reversible with built-in switch
direction of rotation spring-return
reversible with switch
Overload Protection
electronic throughout 0° to 95° rotation
Input Impedance
100 kΩ for DC 2...10 V (0.1 mA), 500 Ω for 4...20 mA, 1500 Ω for PWM, On/Off and Floating point
Quality Standard
ISO 9001
Degree of Protection
IP54, NEMA 2, UL Enclosure Type 2
Nominal voltage
AC/DC 24 V
Power Supply
24 VAC, ±20%, 50/60 Hz, 24 VDC, ±10%
Agency Listing
cULus acc. to UL60730-1A/-2-14, CAN/CSA E60730-1:02, CE acc. to 2004/108/EC and 2006/95/EC
Position Feedback
DC 2...10 V, Max. 0.5 mA, VDC variable
Operating Range
DC 2...10 V (default), 4...20 mA w/ ZG-R01 (500 Ω, 1/4 W resistor), variable (VDC, on/off, floating point)
Emergency control function
Electronic Fail-Safe
Family Series
GK Series
Operating range Y
DC 2...10 V
Control operating range Y note
4...20 mA w/ ZG-R01 (500 Ω, 1/4 W resistor)
Options positioning signal
variable (VDC, on/off, floating point)
Operating range Y variable
Start point DC 0.5...30 V|End point DC 2.5...32 V
Position feedback U
DC 2...10 V
Position feedback U note
Max. 0.5 mA
Position feedback U variable
VDC variable
Noise Level (Fail-Safe)
<45 dB (A) 
Running time (Fail-Safe)
35 seconds
Running Time (Motor)
default 150 sec, variable 95...150 sec
Running Time (Fail-Safe)
<35 sec
Fail-Safe function
Electronic fail-safe
Control type
MFT/Programmable
Connection
cable
Degree of protection IEC/EN
IP54
Degree of protection NEMA/UL
NEMA 2
Enclosure
UL Enclosure Type 2
Tagging function
US|CA
Pre-charging time
5 to 20 seconds
Bridging time
programmable 0...10 sec (2 sec default) delay before fail-safe activates
CP65 Warning
⚠ WARNING: For Belimo Products sold in California, these Products do or may contain chemicals which are known to the State of California to cause cancer and or birth defects or other reproductive harms. For more information see www.p65warnings.ca.gov.

Need Help?

Call one of our experts 1-888-423-2525

Monday-Friday EST 6:00am - 4:00pm