- Maintenance
- maintenance free
- Power consumption in operation
- 12 W
- Power consumption in rest position
- 3 W
- Transformer sizing
- 21 VA (class 2 power source)
- Ambient humidity
- 5...95% r.H. non condensing (EN 60730-1)
- Housing material
- UL94-5VA
- Electrical Connection
- 18 GA plenum cable, 3 ft [1 m], with 1/2" conduit connector, degree of protection NEMA 2 / IP54
- Manual override
- external push button
- Angle of rotation
- Max. 95°, adjustable with mechanical stop
- Noise level, motor
- <45 dB (A)
- Position indication
- reflective visual indicator (snap on)
- Ambient temperature
- -22...122°F [-30...50°C]
- Non-operating temperature
- -40...176°F [-40...80°C]
- Control
- On/Off|Floating point
- direction of rotation motor
- reversible with built-in switch
- direction of rotation spring-return
- reversible with switch
- Overload Protection
- electronic throughout 0° to 95° rotation
- Input Impedance
- 100 kΩ
- Quality Standard
- ISO 9001
- Degree of Protection
- IP54, NEMA 2, UL Enclosure Type 2
- Nominal voltage
- AC 24 V
- Power Supply
- 24 VAC, ±20%, 50/60 Hz
- Agency Listing
- cULus acc. to UL60730-1A/-2-14, CAN/CSA E60730-1:02, CE acc. to 2004/108/EC and 2006/95/EC
- Emergency control function
- Electronic Fail-Safe
- Family Series
- GK Series
- Noise Level (Fail-Safe)
- <45 dB (A)
- Running time (Fail-Safe)
- 35 seconds
- Running Time (Motor)
- 150 sec constant, independent of load
- Running time motor note
- constant, independent of load
- Running Time (Fail-Safe)
- <35 sec
- Fail-Safe function
- Electronic fail-safe
- Control type
- Floating/3-point
- Connection
- cable
- Degree of protection IEC/EN
- IP54
- Degree of protection NEMA/UL
- NEMA 2
- Enclosure
- UL Enclosure Type 2
- Pre-charging time
- 5 to 20 seconds
- Bridging time
- 2 sec delay before fail-safe activates
- CP65 Warning