- Maintenance
- maintenance free
- Power consumption in operation
- 1 W
- Power consumption in rest position
- 0.7 W
- Transformer sizing
- 2 VA (class 2 power source)
- Ambient humidity
- 5...95% r.H. non condensing (EN 60730-1)
- Housing material
- UL94-5VA
- Electrical Connection
- 18 GA plenum cable, 3 ft [1 m], with 1/2" conduit connector
- Angle of rotation
- 90°, adjustable with mechanical stop
- Noise level, motor
- max. 35 dB (A)
- Position indication
- pointer
- Ambient temperature
- 35...104°F [1.7...40°C]
- Non-operating temperature
- -40...176°F [-40...80°C]
- Control
- On/Off|Floating point
- Overload Protection
- electronic thoughout 0° to 90° rotation
- Quality Standard
- ISO 9001
- Degree of Protection
- IP40, NEMA 2
- Nominal voltage
- AC 100...240 V
- Power Supply
- 100...240 VAC, -15% / +10%, 50/60 Hz
- Agency Listing
- cULus acc. to UL60730-1A/-2-14, CAN/CSA E60730-1:02, CE acc. to 2004/108/EC and 2006/95/EC
- Emergency control function
- Non-Spring Return
- Family Series
- CQ
- Running Time (Motor)
- 75 sec
- Fail-Safe function
- Non fail-safe
- Control type
- Floating/3-point
- Connection
- cable
- Degree of protection IEC/EN
- IP40
- Degree of protection NEMA/UL
- NEMA 2
- Enclosure
- UL Enclosure Type 2
- Application
- Non-Spring Return On/Off/Floating Point ZoneTight actuator. Valve selection should be done in accordance with the flow parameters and system specifications. The actuator is mounted directly to the valve without the need for tools or additional linkage. Angle of rotation is adjustable with the integrated mechanical stop.
- CP65 Warning
- ⚠ WARNING: For Belimo Products sold in California, these Products do or may contain chemicals which are known to the State of California to cause cancer and or birth defects or other reproductive harms. For more information see www.p65warnings.ca.gov.
Datasheet Download: Datasheet
Need Help?
Call one of our experts 1-888-423-2525
Monday-Friday EST 6:00am - 4:00pm