SGA24

$111.60

Each

Positioner for wall mounting

or sign up for a free membership to get our lowest pricing.

Weight 1.8 lbs
Brand

Belimo

Protection class IEC/EN
III safety extra-low voltage (selv)
Degree of protection IEC/EN
IP40 (IP54 with cable glands)
Degree of Protection
IP40 (IP54 with cable glands)
Mode of operation
Type 1.B
Material short text
Positioner for wall mounting
Actuator family
Electronic Accessory
Introductory text
For surface mounting
Accessories title
Positioner
Accessories text
Positioner for wall mounting 0…100% operating range selectable DC 0...10 V or DC 2...10 V
Accessories, miscellaneous
0…100%|operating range selectable|DC 0...10 V or DC 2...10 V
Accessories use
for wall mounting
Product family
Positioner
NA Product type
S - Sensors
Structure Level1
Actuators
Structure Level2
Accessories
Ambient temperature
-4...122°F [-20...50°C]
Non-operating temperature
-40...176°F [-40...80°C]
Maintenance
maintenance free
Control operating range Y note
Operating range selectable DC 0...10V or DC 2...10 V
Positioning signal Y note
DC 0...10 V switchable with slide switch
Nominal voltage
AC/DC 24 V
Nominal voltage AC
24 V
Nominal voltage DC
24 V
Nominal voltage frequency
50/60 Hz
Connection
terminals
Connection supply / control
terminals 1.5 mm²
Nominal voltage range
AC 19.2...28.8 V / DC 19.2...28.8 V
Notes box electrical installation
Connection via safety isolating transformer.
Connection Cable
NO
Accessory type
Electrical accessory
Non-Spring
GMB(X)|AMB(X)|NMB(X)|LMB(X)|AHB(X)|LHB(X)|LUB(X)
Electronic fail-safe
NKQB(X)|AHKX
Spring
EFB(X)|AF|NF|TFB(X)|LF
Power consumption in operation
0.3 W
Power consumption in operation [Range]
0.3 W
Easy switching
The switching from DC 2 ... 10 V to DC 0 ... 10 V is accomplished by means of a slide switch on the printed circuit board.
Application
The positioner is used for the (remote) control of modulating damper actuators or as a minimum positioner (lower limitation of output signals from modulating controllers). The adjustment range is 0 ... 100% angle of rotation of the connected actuator.
Safety notes
The device must not be used outside the specified field of application, especially not in aircraft or in any other airborne means of transport. Only authorised specialists may carry out installation. All applicable legal or institutional installation regulations must be complied during installation. The device may only be opened at the manufacturer's site. It does not contain any parts that can be replaced or repaired by the user. The device contains electrical and electronic components and must not be disposed of as household refuse. All locally valid regulations and requirements must be observed.

Need Help?

Call one of our experts 1-888-423-2525

Monday-Friday EST 6:00am - 4:00pm