- Medium temperature
- 15...175°F [-10...80°C]
- Ambient temperature
- 15...120°F [-10...50°C]
- Output signal active note
- current output: max. 900 Ω load
- Power supply DC
- 15...24 V
- Power supply tolerance DC
- ±10%
- Power consumption DC
- 0.5 W
- Measuring values
- differential pressure
- Sensor type
- pressure
- Application
- Pipe
- Cable entry
- angle plug according to DIN 43650, construction A
- Electrical connection
- Connector Plug for wire 0.5...1.5 mm²
- Ambient humidity
- max. 95% r.H. non-condensing
- Mounting
- installation position unrestricted
- Mounting instruction
- Mounting instruction - 71937-00001B 22WDP
- Degree of protection IEC/EN
- IP65
- Degree of protection NEMA/UL
- NEMA 4
- Degree of Protection
- IP65, NEMA 4
- Certification IEC/EN
- IEC/EN 60730-1
- Protection class IEC/EN
- III protective extra-low voltage (pelv)
- Protection class UL
- UL Class 2 Supply
- Quality Standard
- ISO 9001
- Material short text
- Water Diff Pressure Sensor 100psi A
- Output signal
- 4...20 mA
- Housing
- base: stainless steel 1.4305|cover: aluminum pressure die casting
- Optional accessories
- A-22WP-A03|A-22WP-A05|A-22WP-A07|A-22WP-A09
- Electrical connection note
- for wire 0.5...1.5 mm²
- Connection
- Connector Plug
- Product family
- Sensor
- CAD data 3D
- Belimo_22WDP-135_3D.dwg|Belimo_22WDP-135_3D.dxf|Belimo_22WDP-135_3D.igs|Belimo_22WDP-135_3D.sat|Belimo_22WDP-135_3D.stp
- Measuring range rel. pressure
- 0...100 psi
- Accuracy pressure
- <±1% of measuring range @ 23...167°F [-5...75°C]
- Measuring media
- air and non-aggressive gases
- Mechanical connection
- pressure connector: 1/4" NPT
- Housing seal
- EPDM
- Medium wetted parts
- stainless steel 1.4301, ceramic
- Dynamic response
- Suitable for static and dynamic measurements. Response time: <10ms
- Maximum System pressure
- 300 psi
- Overpressure range
- 230 psi
- Overpressure range note
- Single-sided
- Output signal active pressure
- 4...20 mA
- Application text
- Active sensor (4 to 20 mA) for measuring the differential pressure in liquid or dry media. Various pressure ranges, rugged NEMA 4 / IP65 and compact stainless steel housing. Optional stainless steel or brass pipe connection adapters also available.
- General caution
- The installation and assembly of electrical equipment should only be performed by authorized personnel. This device has been designed for use in stationary heating, ventilation and air conditioning systems and must not be used outside the specified field of application. Unauthorised modifications are prohibited. The product must not be used in relation with any equipment that in case of a failure may threaten human, animals or assets. Ensure all power is disconnected before installing. Do not connect to live/operating equipment.
- Additional caution
- Please comply with • Local laws, health & safety regulations, technical standards and regulations • Condition of the device at the time of installation, to ensure safe installation • This data sheet and installation manual
Datasheet Download: Datasheet
Installation instructions Download: Installation instructions
Need Help?
Call one of our experts 1-888-423-2525
Monday-Friday EST 6:00am - 4:00pm